Cleaver Brooks CB-700-300-15ST

The Cleaver Brooks CB model is a skid-mounted packaged boiler complete with the boiler, integral burner, and all required controls and safety equipment. This CB is a four-pass dry-back firetube boiler, constructed to ASME Section IV code and utilizing 5 sq ft per BHP of surface area per boiler horsepower.

This boiler was purchased by Powerhouse from a customer who was replacing these boilers with new ones. This boiler has since been fully reconditioned and tested for a new customer. Our reconditioning process verifies that this boiler is 100% functional and ready for many more years of service which is why we offer a 1-yr warranty that matches or exceeds the original factory warranty.

Specs

Brand

Cleaver Brooks

Boiler Type

Firetube

Output Capacity

2,588 - 10,350 PPH
Max Pressure 0 - 15 PSIG
Fuel(s) Natural Gas
Service Saturated Steam
Emission Rating 100 ppm

Need a quote?

TECHNICAL SPECIFICATIONS

GENERAL DESIGN CAPACITIES & INPUTS BURNER & ELECTRICAL DIMENSIONS & WEIGHTS
MANUFACTURER (OEM) CLEAVER-BROOKS OUTPUT CAPACITY 10,350 LB/HR BURNER MANUFACTURER (OEM) CLEAVER-BROOKS OVERALL LENGTH 18' 7-1/2"
YEAR 1998

HORSEPOWER

300 BHP
MODEL
INTEGRAL OVERALL HEIGHT 8' 10"
SERIAL NO. 0L097371 DESIGN PRESSURE (MAWP) 15 PSIG TYPE FULL MODULATION OVERALL WIDTH
8' 7"
NATIONAL BOARD NO. 9136 OPERATING RANGE 3-12 PSIG FLUE GAS RECIRCULATION (FGR) NO SHIPPING WEIGHT 24,000 LBS
CRN NO. TBD HEATING SURFACE 1,500 FT² ELECTRIC 460V/3PH/60HZ OPERATING WEIGHT 37,000 LBS
MODEL CB-700-300-15 MAX. FUEL INPUT 12,553,000 ATOMIZATION NONE BOILER OUTLET 12" Ø 150# R.F. FLG.
ASME CODE SECTION - STANDARD FUELS NATURAL GAS CONTROL TYPE SINGLE-POINT POSITIONING EXHAUST OUTLET 20" Ø OD
TYPE SCOTCH ADDITIONAL FUELS #6 FUEL OIL BOILER CONTROL SYSTEM -    
DESIGN FOUR-PASS DRY BACK FIRETUBE INPUT GAS PRESSURE 15.5" WC MINIMUM BURNER MANAGEMENT SYSTEM CB780    
MOUNTING SADDLES & SKID-MOUNTED TURNDOWN RATIO 4:1 FLAME SAFEGUARD IR SCANNER  

INTERNAL CORRUGATED FURNACE & STRAIGHT RIFFLED TUBES EMISSION RATING (NOX) 100 PPM UNCONTROLLED BLOWER MOTOR 7.5 HP TEFC    
    EMISSION RATING (NOX) #2 - BURNER INSTALLED YES    
        PILOT TYPE NG / PROPANE    
        INSTRUMENT AIR NONE    
        AIR COMPRESSOR NOT REQUIRED